Abstract
Performance of the heat pump with attaching an air heat exchanger was investigated in the heating condition when the air heat exchanger was worked in the ambient air temperature of -5 to 11$\^{C}$ and air flow rate of 542 to 747 ㎡/h. Performance tests for heating condition were conducted in an experimental room equipped with heat pump. The performance tests were performed in a ambient temperature of -4 ∼ 11$\^{C}$, and room temperature of 4∼22$\^{C}$ respectively. Measured data(temperature, capacity of heat transfer and consumption of electronic power) were analyzed to the efficiency of HEEVA(Heat Exchanger fur the Evaporator), overall heat transfer coefficient and COP of heat pump. The results of inlet temperature for evaporator increased that the temperature was 2 ∼6$\^{C}$, and inlet temperature for condenser decreased that the temperature was 3 ∼ 8$\^{C}$. The results of comparing efficiency of HEEVA for the ratio of heat exchange between hot air and cold air showed that efficiency were considered to 91% because of the ratio of 83∼98%. The results of comparing of COP for the heat pump increased that improvement COP was approximately 0.3∼7.5 than HEEVA had not been operated.