Analysis of Harmonic Effects on Substation Power System and its Countermeasure

지하철 전력계통의 고조파 영향 분석 및 그 대책에 관한 연구

  • 송진호 (명지대학 정보제어공학과) ;
  • 황유모 (명지대학 정보통신공학부)
  • Published : 2002.04.01

Abstract

We analysised the effect of harmonics on electric machines of substation power system barred on quantitatively measured harmonics and proposed the methods for prevention of harmonics through checking on transformer, rectifier and cable's capacities against harmonics with reference to KEPCO's electricity service standard. In order to analysis harmoninics of silicon rectifier that is power source in DC substation, computer simulations for a substation with TR of high voltage distribution switchboard are performed. Simulation results show that the total harmonic distortion factor becomes smaller for TR primary and receiving points in order rather than silicon rectifier which is harmonic generation source so that the harmonics generated frets each rectifier are outflowed to power supply and high voltage distribution switchboard The result of higher distortion factors of voltage and current for rectifier with 100% load than those with 50 % and 30% indicates that the waveform of voltage and current for the real substation power system at the office-going and the closing hours with heavy loads might be more distorted. As proposed methods for harmonic reduction, the conventional 6 pulse-type for substation is required to be replaced by 12 pulse-type for reduction of 5th and 7th harmonics. The active filter rather than the passive filter is more effective due to severe variance of rectifier loads, but the high cost is price to be paid. In view of installation area and costs, the use of 12 pulse-type transformer is desirable and then the parallel transformer and the rectifier within the substation must be replaced at the same time. Other substations with parallel feeder can use 6 pulse-type transformer.

Keywords

References

  1. 배전계통 고조파 장해 방지대책', 電氣協同硏究會, 第38券, 第 3號, pp.1-184, 1981
  2. 송진호, '수전설비의 고조파 진단과 대책에 관한 연구', 공학석사학위논문, 인하대학교 산업기술대학원, 1996. 11
  3. '전력케이블의 허용전류', 일본전선공업규격(JCS-168-C), 1973
  4. 유상봉, '전기설비에서의 고조파 대책 기술', 조명전기설비학회지, 특집:전기설비의 EMI/EMC, 13권, 4호, pp.40-52, 1999
  5. '국내 고조파 관리 기준', 한국전력 전기공급규정, 1999
  6. 고주파 억제 대책 기술 지침', JPEG9702, 일본통산성, 1997
  7. 고주파 발생원에서의 대책', 月刊電氣, 通卷 第 86 號, pp.31-39, 1995
  8. T. Karaoka, K. Mizumachi, and S. Miyari, 'A pulse width controlled AC to DC converter to improve power factor and waveform of AC line current', IEEE Tran. IA-15, pp.670-675, 1979
  9. D. Maischak, 'A novel control stategy for IGBT-Four-Quadrant converter', pp.3179-3183, EPE'97
  10. '구미제국의 고조파 억제대책의 상황', 月刊電氣, 通卷 第 95 號, pp.46-50, 1996
  11. Giuseppe S. Buja, 'Optimum Output Waveforms in PWM Inverters', IEEE Trans. on IA, vol.IA-16, no.6, pp.830-836, 1980