A Study on the Electromagnetic Transients at Switching Capacitor Banks in a Electric Distribution Electric Power Distribution Substation

배전변전소에서 캐패시터 뱅크 투입시 일어나는 전자과도 현상에 관한 연구

  • 김경철 (홍익대학교 전자전기컴퓨터 공학부)
  • Published : 2002.01.01

Abstract

Transient in an electric distribution system are mainly generated by switching. This paper presents analysis of switching surge and means of limiting the voltage magnification transient for high voltage power systems by using the EDSA's EMTAP software package. One means of limiting the voltage magnification transient is to convert the end-user power factor contraction capacitor banks to harmonics filters. An inductance in series with the capacitor bank was used to decrease the transient voltage at the customer bus to acceptable levels. And also simulation results used the EDSA harmonics analysis program show the effect of harmonics reduction.

배전변전소에서 과도현상은 주로 스위칭으로 인해 발생한다. 본 논문에서는 스위칭 서지 현상을 분석하고, 과도현상을 저감시키는 방법을 상용화된 EDSA의 EMTAP 프로그램을 이용하였다. 과도현상으로 인한 전압의 크기를 제한하는 방법으로 부하측의 역률개선용 캐패시터 뱅크를 노조파 필터로 변환시켰다. 캐패시터 뱅크에 직렬로 연결된 인덕턴스는 부하측에 적절한 수준의 전압으로 낮출 수가 있었다. 또한 EDSA의 고조파 분석 프로그램으로 시뮬레이션한 결과는 고조파 저감 효과도 검증할 수 있었다.