Journal of the Korean Society of Safety (한국안전학회지)
- Volume 16 Issue 4
- /
- Pages.1-6
- /
- 2001
- /
- 1738-3803(pISSN)
- /
- 2383-9953(eISSN)
Emission Characteristics of LP Gas Burner for the Variation of Combustion Conditions
연소조건 변화에 따른 LP가스버너의 배기특성
Abstract
An experimental study was carried out to investigate the emission characteristics of LP gas burner for the Practical combustion conditions including fm voltage, inlet area, gas Pressure, emission resistance, duct length and height. The result shows that CO is almost remains constant for the emission fan voltage, but significantly increases with the reduction rate of air inlet, up to 3000ppm at 50% of reduction rate. Also, the variation of gas pressure has no effect to CO of gas boiler due to its governor which controls gas pressure secondly, but it gives an rapid increase of CO for the gas range. The emission resistance test shows that CO is suddenly increased with the reduction rate of emission duct above 70% and main burner is stopped at 90%. The reverse wind test shows that CO is suddenly increased with the air velocity above 7m/s and main burner is stopped at 9m/s. The more horizontal length of emission duct is long and the vertical height is low, CO is infinitesimally increased.