A Study on the Harmonic of the electrical Installations in Apartment Housing
아파트 전기설비에서의 고조파 실태 분석 연구
Abstract
To analysis the effect by the Harmonics through Power facilities in Apartment housing, This paper measured the Harmonics at Lighting Transformer, Power Transformer and Services-entrance Conductors of electrical installation in apartment housing. The measured result is following as : 1) The Harmonics at Lighting Transformer is generated in the large of the 5th Harmonics. 2) The Harmonics at Power Transformer is generated in the large of the 5th and 7th Harmonics. And then 3) The THD at the Services-entrance Conductors is average 2.4[%], which is compared to the measuring Voltage, this meaning value is good condition until now against Harmonics effect. But, So the large capacitance of household electrical alliances with rectifiers in the future considered the effect of Harmonics at the Electric Power planning in apartment Housing.
본 연구에서는 아파트의 각종 전력설비에서 고조파 실태와 영향을 파악하기 위하여 이를 측정하고 분석하였다. 그 결과 세대에 전력을 공급하는 전등전열변압기에서는 제5고조파, 동력변압기에서는 제5고조파 및 제7고조파가 많이 발생되는 것으로 분석되었다. 또한 아파트 수변전설비의 인입점에서 측정한 전압의 종합왜형률(THD) 은 평균 2.4[%]로서 비교적 양호한 것으로 나타났으나, 향후 가전기기의 대용량화 추세에 따라 아파트의 전력설비 계획에서도 고조파에 대한 고려가 필요한 것으로 분석되었다.