A Study on the Characteristic of Power Consumption and Design of the Electrical Installations for the Inverter Controlled Elevator
인버터제어 승강기의 전력소비 특성과 전원설비 계획에 관한 연구
Abstract
This paper analysed the characteristic of Power consumption at many type of Inverter controlled Elevator. Especially, this paper proposed the standard value of full load currents. For this propose, it was classified by the passenger capacity and manufacture company. As a result, it is found that (i) the value is between -3[A] and 7[A] in case of elevator. That means the full load currents was smaller than the standard value of conventional operation type (ii) the value is between 0.5[kVA] and 3[kVA] in case of Power transformer. That means the transformer capacity was smaller than the standard value of conventional operation type. it was classified by the passenger capacity at inverter controlled elevator in apartment Also, to guarantee the operation stop of inverter controlled elevator, this paper proposed the redundancy method of electrical installations. the redundancy method is (i) 2 line service system and (ii) 2 distribution line system.
본 연구에서는 다양한 기종의 인버터제어승강기 전력소비특성을 분석하였다. 특히, 전부하상승전류는 기종별로 표준적인 기준치를 제시하였으며, 그 결과 아파트에 시설되는 인버터제어 승강기의 경우, 전부하상승전류의 크기는 기종별로 기존의 기준치 보다 -3[A]∼7[A] 정도 작아지는 결과을 얻었으며, 동력변압기 용량은 기종별로 기존 기준치 대비 약 0.5[kVA]∼3[kVA] 정도 작은 용량이 적정 용량인 것으로 분석되었다. 또한 전원설비 계획으로서 인버터제어 승강기의 운행 정지사태를 최소화하기 위한 2회선 수전방식 및 2계통 배전 등의 다양한 전원확보방안을 제시하였다.
Keywords