한국화재소방학회논문지 (Fire Science and Engineering)
- 제15권2호
- /
- Pages.46-52
- /
- 2001
- /
- 2765-060X(pISSN)
- /
- 2765-088X(eISSN)
스프링클러 반응시간 예측에 대한 화재모델의 비교
A Comparison of the Prediction of Sprinkler Response Time Applying Fire Models
초록
To evaluate the usability of compartment fire models for predicting sprinkler response time, fire experiment was conducted and measured sprinkler response time. The experimental data was compared with zone model "FASTLite"and field model "FDS"and field Model "SMARTFIRE" A Compartment fire conducted in a 2.4 m by 3.6 m by 2.4 m ISO 9705 room and measured H.R.R was approximately 100.3 kW. In test, Sprinkler activation temperature used is