A Study on the Fire Spread between Office Room and Atrium in the Atrium Building

아트륨 빌딩에서의 사무실과 아트륨간의 화재확산에 관한 연구

  • Lee, Su-Kyung (Department of Safety Engineering, Seoul National University of Technology) ;
  • Kim, Jong-Hoon (Department of Safety Engineering, Seoul National University of Technology)
  • 이수경 (서울산업대학교 안전공학과) ;
  • 김종훈 (서울산업대학교 안전공학과)
  • Received : 1999.08.10
  • Accepted : 2000.05.22
  • Published : 2000.06.30

Abstract

Generally, There is to install fire resist shutter or to compart between the office room and the atrium in the atrium buildings in Korea. But, Glass wall that is installed sprinkler which purpose to protect it from fire, is already installed between the office room and the atrium in the advanced nations. We study this problem as follow; We made the fire scenario, and analyze each scenario using FASTLite is fire modeling software and BREAK1 is to predict the window breakage time in the compartment fire. In this study, we can decide that fire compartmentalization between atrium and office rooms doesn't require in Atrium building if the material and fire protection system were reliable. Consequently, Korean Fire Protection Regulations have to consider in direction of increasing freedom of building.

일반적으로 국내에서는 아트륨과 사무실 공간 사이를 내화구조로 하거나 방화셔터를 설치하고 있다. 그러나 선진외국에서는 이미 아트륨과 사무실 공간 사이에 유리벽을 설치할 수 있도록 하고 있다. 단, 유리벽면을 따라 방호용 스프링클러를 설치한다는 조건에서 이다. 본 연구는 이러한 문제점에 대하여 다음과 같이 진행하였다. 각 시나리오에 대하여 화재 시뮬레이션 프로그램인 FASTLite와 BREAK1을 사용하여 화재 전파 및 위험성을 분석하였다. 결과적으로 아트륨과 사무실간에는 아트륨의 규모가 크고 상부가 충분한 연기와 열기의 조정이 가능하고, 창문을 사이에 두고 일정간격으로 스프링클러 헤드를 설치하여 충분히 화재로부터 유리를 보호할 수 있는 경우 방화구획으로 인정 해주어야 할 것이다. 또한 충분한 연기와 열의 제어가 가능한 것이 공학적인 화재분석방법을 통해 인정받은 경우에는 아트륨과 주변 사무실간의 완전개방도 검토되어야 할 것이다.

Keywords