저온공조용 잠열 축열조의 열전달 특성에 관한 실험적 연구

An Experimental Study on Heat Transfer Characteristics in the LHSS for Cool Thermal Air Conditioning

  • Seo, I.H. (Graduate School, In-ha University) ;
  • Koh, J.Y. (Graduate School, In-ha University) ;
  • Lee, C.M. (Dept. of Mechanical Eng., Yuhan College) ;
  • Yim, C.S. (Dept. of Mechanical Eng., In-ha University)
  • 발행 : 2000.09.30

초록

In this study, the basic data which were required for development of LHSS(latent heat storage system) were experimentally obtained. Experiments were carried out under the following conditions. The initial temperatures of P.C.M. which were used by parameter is $5^{\circ}C,\;9^{\circ}C$ and $14^{\circ}C$. The conditions of working fluid are $-6^{\circ}C,\;-4^{\circ}C$, and $65{\ell}$/min.. The pure water of which the freezing point is $0^{\circ}C$ was filled in the system, and the Ethylene glycol(brine) was circulated through the 10 vertical tubes as a secondary fluid in order to cool the P.C.M. down. The inlet temperature of the secondary fluid and the initial temperature of the water were varied to investigate the effects of the important design parameters. The phenomenons of temperature conversion of P.C.M. were appeared for the conductive heat transfer and free convective heat transfer by buoyancy force in this storage unit system. In order to find the effective water circulation path, we obtained P.CM. temperature distributions of 5 parts in the storage tank during freezing process.

키워드