A Study on the Heat Transfer Performance Using Various Grooved Heat Transfer Tubes

다양한 전열관 내부 홈 변화에 의한 열전달 성능에 관한 연구

  • Published : 2000.02.28

Abstract

Single-phase heat transfer performance and pressure drop for internally grooved tubes with angles were studied. Experiments were carried out in a counter flow heat exchanger with water as a working fluid. Two commercially available internally grooved tubes and smooth tube were tested. The internal diameter of the smooth tube was 16.5mm and the internal diameters of grooved tubes were 15.4mm, 14.9mm, 15.0mm, 16.7mm, respectively. Grooved angles in the tubes were $37^{\circ},\;43^{\circ},\;45^{\circ},\;50^{\circ}$, respectively. An experimental device to measure the friction factor and heat transfer coefficient was constructed. The experimental results were obtained for the fully developed turbulent flow of water in tube on the condition of uniform heat flux. As the increase of flow rate, Reynolds number, numbers of groove and grooved angle led to the increase of pressure drop. Also this paper showed that heat transfer rate increased with increasing numbers of groove and grooved angle. An empirical relation taken from this study represented most of the data within ${\pm}25%$.

Keywords