Abstract

The characteristics on the interface between Epoxy and EPDM which are materials of the underground insulation systems of power delivery have studied. The breakdown strength of specimens are observed by applying high AC voltage at the room temperature. The breakdown times under the constant voltage below the breakdown voltage were gained. As constant voltage is applied the breakdown time is proportion to the breakdown strength. The life exponent n is gained by inverse power law and the long breakdown life time can be evaluated. AC breakdown strength and life time is improved by oiling to the interface. When the low viscosity oil is spread interface has the highest life time.

Keywords

References

  1. Journal of the KIEEME v.12 no.12 Dielectric Breakdown Phenomenon of the Interface between Epoxy/EPDM Duck-Kweon Bae(et al.)
  2. IEEJ National Convention no.1601 Stability of interfaces for prefabricated joint H. Nakanishi(et al.)
  3. IEEE Trans. on Power Delivery v.11 no.2 Stability on Detection for the Defects of XLPE Cable Lines Katsumi Uchida(et al.)
  4. IEEE Trans. on Electrical Insulation v.28 no.5 The Statistic of Aging Models and Practical Reality G. C. Stone
  5. 固體 絶緣材料の 界面效果 日本 電氣學會 技術 報告 固體 絶緣材料の 界面效果 調査 專門委員會(編)
  6. CIGRE Development of a 420kV XLPE Cable System for the Metropolitan Power Projection in Copenhagen P. Andersen(et al.)