A Study of Surge Pressure Absorption by Water Hammer Arrester in Water Supply Piping System

워터 햄머 흡수기의 압력흡수 효과에 관한 연구

  • Published : 2000.12.01

Abstract

This study is to investigate the pressure wave characteristics and the absorption of maximum and minimum pressure generated by instantaneous valve closure at the end of the straightening copper piping system with and without a water hammer arrester. Experiments were conducted under the following conditions : initial pressure 1~5 bar, flow velocity 0.6~3.0 m/s, water temperature $20^{\circ}C$ and air volume of water hammer arrester $80~180^cm^3$. Experimental results show that the optimum air volume of water hammer arrester is 110㎤.

Keywords

References

  1. Journal of Air-Conditioning and Refrigeration v.5 Effects of waterhammer arresters and air chambers in a simple water piping system of buildings Han, H. T.;Kim, J. M.
  2. E. J. Zimmer Technical Seminar Water hammer control Ballanco
  3. ANN ARBOR SCIENCE Modern Analysis and Control of Unsteady Flow in Pipelines Gray Z.;Watters
  4. ANSI/ASME A112.26.1M Water Hammer Arresters The American Society of Mechanical Engineers
  5. Korean Journal of Air-Conditioning and Refrigeration Engineering v.12 no.7 The experimental study of water hammer by valve closure in water supply piping system Lee, Y. H.;Yoo, J. O.;Park, H. S.;Kim, Y. H.
  6. Transactions of the society of heating, air-conditioning the sanitary engineers of Japan no.4 A study on water hammer and prevention in water supply piping system of building Noriyuki Takahashi;Fumitoshi Kiya
  7. Proceedings of the society of heating, air-conditioning the sanitary engineers of Japan A fundamental study of the water hammering in hot water supply pipes Kuwahara Takumi(et al.)