Abstract
This paper presents the results of cyclic seismic performance in relation to beam-panel zone strength ratio of CFT Column to H-beam steel moment connections. Each test specimen consisted of $H-350{\times}175{\times}7{\times}11$ beam(SS400) and ${\boxe}-250{\times}250{\times}9$, ${\boxe}-250{\times}250{\times}12$ column(SPSR400). Main parameter is a column panel zone strength relative to beam strength. Energy absorption capacity available in the specimens ranged from 5.2 to 12.7(tm). If panel zone strength relative to beam strength is too strong or weak, the energy absorption capacity tended to be inferior. About steel moment-resisting frame, the test results of this experiment seem to support the investigation that permitting panel zone yielding shall be more advantageous to enhancing total seismic performance.
본 논문은 CFT기둥-H형강보 철골 모멘트 접합부의 보-패널존 강도비에 의한 내진거동을 평가하였다. 보에 대한 패널존의 상대강도를 주요변수로 하였다. 각 실험체는 $H-350{\times}175{\times}7{\times}11$ 보(SS400)와 ${\boxe}-250{\times}250{\times}9$, ${\boxe}-250{\times}250{\times}12$ 기둥(SPSR400)으로 제작되었다. 실험체의 에너지 흡수량은 5.2~12.7(tm)의 분포를 나타냈다. 패널존이 보에 비해 너무 강하거나 약하면, 에너지 흡수능력이 열등했다. 철골 모멘트 저항골조에 있어서 본 실험의 결과는 패널존의 항복을 허용하는 것이 내진거동에 유리함을 나타내고 있다.