A Study on Backwashing of Granular Fiters Used in Water Treatment

정수처리를 위한 여과지의 역세척에 관한 연구

  • Published : 1999.06.15

Abstract

To obtain the experimental data for design and operation of actual filtration processes, a sand filter and three kinds of dual media filters in pilot-plant scale were operated in this study. We analyzed the effect of filter medium composition on the filter performance and the effects of backwash water flow rates, length of stream line and air flow rate on the filter backwash efficiency. We also compared the efficiencies of the combined air-water backwashing and the water backwashing in dual media filters. As the backwash water flow rates or the length of stream line increased, the final turbidity of backwash water was decreased and the filtration duration time after backwash was increased. In the case of the combined air-water backwashing, the backwash water quantity needed for backwashing the dual media filters could be decreased. The total volume of filtered water for the dual media filters during filter run was over three times larger than that for the sand filter. The dual media filters could be operated at a high filtration rate of 360 m/day.

Keywords