Application of a Large Scale Heat Pipe System to Preheating the Fuel Gas of Low Heating Value

분리형 히트파이프의 저발열량 연료가스 예열시스템에 대한 적용연구

  • 박흥수 ((재)포항산업과학 연구원) ;
  • 유갑종 (경북대학교 기계공학부) ;
  • 이진호 (육군제3사관학교 기계공학과) ;
  • 이용국 ((재)포항산업과학 연구원)
  • Received : 1998.06.08
  • Published : 1999.09.01

Abstract

A separate heat pipe system capacity of 3,700kW has been developed and applied to preheating the blast furnace gas for recovery of the waste heat from boiler. The system is designed to preheat the blast furnace gas up to $126^{\circ}C$ by using tho boiler exhaust gas of which temperature is $180^{\circ}C{\sim}220^{\circ}C$. The arrangement of the fin tubes as well as the shape of the fin has been carefully determined to minimize the fouling problems. The heat pipe system was found to be stable in circulation of the working fluid and the range of the temperature variation of the preheated blast furnace gas was within $10^{\circ}C$. It was proved through a long-term test that the selected tube arrangement and the shape of the fins are proper to prevent the fouling problems and that the pay-back period of the system Is within one year.

Keywords