가정용 흡수식 냉난방기 개발을 위한 재생기 성능실험

Performance Experiment of Generator for Household Absorption Chiller and Heater

  • 유선일 (한국가스공사 연구개발원) ;
  • 권오경 (부경대학교 대학원 냉동공학과) ;
  • 윤정인 (부경대학교 냉동공조공학과)
  • 투고 : 1999.03.31
  • 발행 : 1999.10.01

초록

Recently, the markets of the air conditioner are enlarging. The market size will reach 2.0 billion won in 2000. Electric heat pumps have been utilized as main residential air conditioners. especially in Korea. They cause a surge up electric power demand during summer. Moreover, the use of HCFCs and HFCs causes serious problem to the global environment such as global warming and ozone layer destruction. Absorption chiller and heater could solve such problems. It was built and tested for analyzing the performance of the generator for absorption chiller and heater. Experiment was done with a high temperature generator, a low temperature generator, heat exchangers, a condenser and a solution tank. It was tested that the double effect series flow cycle with two kinds of solution cycle. Solution cycle B showed better than solution cycle A. Two kinds of heat exchanger were used, where one's heat transfer area is bigger than the other. Bigger one increased a little performance of absorption chiller and heater. But it was not economical. From this study, we got that the coefficient of performance(COP) is 0.82 and the capacity is 7.24 kW for an absorption chiller and heater.