Performance Analysis of an Earth Coupled Heat Pump System Operated by an Engine(III) - Operating Characteristics of a Vapour Compression type Heat Pump Using Alternate Refrigerant -

엔진구동 지열 열펌프의 성능 분석(III) - 대체냉매를 이용한 증기압축식 열펌프의 운전특성 -

  • 김영복 (경상대학교 농업기계학과, 농어촌개발연구소) ;
  • 이승규 (경상대학교 농업기계학과, 농어촌개발연구소) ;
  • 김성태 (경상대학교 농업기계학과, 농어촌개발연구소) ;
  • 송대빈 (경상대학교 농업기계학과, 농어촌개발연구소) ;
  • 강호철 (경상대학교 농업기계공학과)
  • Published : 1999.12.01

Abstract

This study was performed to get the optimal operating conditions of an water-air compact heat pump system using R-134a. The experiments was done for three elvels of the air mass flow rate and the compressor driving speed during air-heating process. The temperature of the air at the condenser inlet and outlet was 17~23$^{\circ}C$, 36~44$^{\circ}C$, respectively. The average temperature of the refrigerant at the evaporator and condenser was 1$0^{\circ}C$, 6$0^{\circ}C$, respectively. The temperature of the refrigerant was not depending on the air mass flow rate and the compressor driving speed. The pressure of the refrigerant at the condenser inlet and outlet was ranged of 10~18.5kg/$\textrm{cm}^2$ and that at the evaporator was ranged of 3.1~3.3kg/$\textrm{cm}^2$. The pressure drop at the condenser and evaporator was about 1.5, 1.2 kg/$\textrm{cm}^2$, respectively. The performance of coefficient for air heating was about 3.3~4.0.