초록
The purpose of the study is to investigate the effect of H$_2$ pressure on partial discharge (PD) activity and aging rate in turbine generator winding insulations. A series of field tests and laboratory tests were peformed to investigate the effect of $H_2$ pressure on PD activity. Field tests were conducted at two unit turbine generators in two conditions, in $H_2$ pressure and in air atmosphere. Obtained results are as follows ; 1) ${\Delta}tan{\delta}$ and maximum partial discharge are reduced with increase of $H_2$ pressure and partial discharge inception voltage. 2) The reduction ratio of ${\Delta}tan{\delta}$ due to $H_2$ pressure is higher than one of PD magnitude. 3) Partial discharge pulses suffer from attenuation and distortion when transmitted along windings, because of the complex L-C network between windings. From the result, partial discharge pulses are subjected to resonance phenomena in a generator winding.