Abstract
The correlation between propagation of electrical tree and internal partial discharges is discussed. We use specimens with needle-plane electrode system made of LDPE(Low Density Polyethylene), observed inception and propagation of electrical tree by optical microscope and investigated the characteristics of the partial discharge (PD) pulses accompanying with propagation of electrical tree. In the specimens with needle-shaped void, the tree propagates branch type. The length of the tree has good linear relation with average discharge power of PD pulses. In the specimens without needle-shaped void, the tree grows bush type tree. The correlation between the area of the tree and the average discharge power of PD pulses has linear relation.
전력용 케이블은 전선로의 지중화 추세에 따라 사용이 증가하고 있다. 케이블 절연체의 경우 장기간의 전압인가에 의해 열화 및 절연파괴 된다. 전력용 케이블의 절연파괴시 발생하는 사회/경제적 문제는 매우 심각한 것으로 알려져 있다. 절연체의 열화에 영향을 주는 요인은 매우 복잡하지만 그중에서도 전기트리 열화에 의한 파괴는 비교적 두꺼운 고체 유전체인 경우에 절연파괴 사고의 주된 원인이 되고 있다. 전기트리의 개시나 진전시 부분방전이 발생하므로 부분방전의 검출에 의해 전기트리의 발생 및 진전 양상을 관측할 수 있고 부분방전의 해석에 의해 절연재료의 잔여 수명을 예측할 수 있다. 본 논문에서는 고전압 전력용 케이블 절연재로써 광범위하게 사용되고 있는 저밀도 폴리에틸렌 시편에서의 전기트리 진전 양상을 비파괴 진단 기법에 의하여 검출하고자 내부 부분방전을 관측/해석하였다.
Keywords