이산화탄소와 R134a의 혼합냉매를 이용한 오토캐스케이드 냉동시스템의 성능

Performance of autocascade refrigeration system using carbon dioxide and R134a

  • 박수남 (서울대학교 정밀기계설계공동연구소) ;
  • 김민수 (서울대학교 기계공학과)
  • 발행 : 1999.11.01

초록

The purpose of this study is to investigate the performance of an autocascade refrigeration system using the refrigerant miktures of R744 (carbon dioxide) and R134a (1,1,1,2-tetrafluoroethane) as working fluids by simulation and experiment. Cycle simulation using a constant UA model in heat exchangers has been performed for R744/134a mixtures of the compositions in the range of from 10/90 to 30/70 by weight percentage. Variations of mass flow rate of refrigerant, compressor work, refrigeration capacity and COP with respect to mass fraction of R744/134a mixture were presented. Performance test has been executed in an autocascade refrigeration system by varying secondary fluid temperatures at evaporator and condenser inlets. Experimental results show similar trend with those from the simulation.