Currently, conventional fire prevention facility installation standard is based on the use and size of the domestic theaters. In the study, theaters with 1,900 seats were examined to suggest a suitable method to adapt a better fire preventing system. The proposed systems are as follow. - 100% of backup pressed-water outlet device, considering waterproof pressure for fire prevention facility at the top floor. - The supplement of the side wall type header and a large caliber outlet header for stage open sprinkler. - Subdividing a installation rule for special detector and implementing the latestdetector. - Installation of fire curtain for dividing stage area and auditorium area, and also the method of installation of fire curtain.

건축물의 면적과 용도에 따른 형식적이고 획일적인 소방시설의 설치기준에 대하여 국내공연장들의 소방 시설 실태를 근거하여 건축물의 특이성에 적합한 방재시설에 대한 보완방법을 신축하고 있는 1900석 규모의 공연장을 사례로 하여 - 최 상층부 소방시설의 방수압력을 고려한 1차 수원의 100%와 예비 가압송수장치 -무대부 개방형 스프링쿨러에서의 측벽형 헤드 보완과 대구경 살수 헤드 -특수감지기의 설치규정 세분화와 첨단 감지기 도입 -무대부와 객석부의 방화구획용 방화막의 설치와 설치에 따른 설치방법 등에 대해 제시하였다.