초록
We have performed an EMTDC simulation for the current limiting effects of a superconducting fault current limiter (SFCL). The fault currents in the 154 kV transmission line between the arbitrary S1 and S2 substations increased up to 54 KA and 60 KA during the line-to-line and three phase faults, respectively. The SFCL with 100$\omega$ of resistance after quench limited the currents to less than 17 KA within a half cycle. This limited current is well below the upper limit of a circuit breaker, suggesting that the resistance of the SFCL in the transmission line is sufficient.