Abstract
Measurerments of ultrasonic signals caused by corona discharges were perforrred by using an ultrasonic meeasurerment technique to analyze the deve1qxrent states of coronas in a high-voltage power apparatus. We also examined the relationship between discharge magnitude and ultrasonic pulse number to diagnose the deterioration of electrical insulation by corona discharges. From these results, it was found that ultrasonic signals due to corona discharges can be firstly detected at the peak value of positive polarities prior to the breakdown voltages, and the magnitude of ultrasonic signals was closely related to the current pulses by the corona discharges when ac voltages were gradually raised, and it appeared that ultrasonic pulse number was proportional to discharge magnitude. Attenuation, tirre-delaying and directivity charocteristics of ultrasonic signals propagated to air by using ultrasonic oscillation and receiving systems are feJXlrt.ed as a basic data of ultrasonic measurements in out-door HV apparatus.aratus.
본 연구는 고전압 전력기기에서 코로나에 의한 절연열화를 진단하기 위해 초음파 측정법을 사용하여 코로나의 진전상태에 따른 초음파신호를 분석하였으며, 또한 방전전하량과 초음파 펄스수의 관계를 조사하였다. 실험결과, 교류전압 인가시 코로나가 성장하여 브러시 또는 스트리머 코로나 형태에서 초음파신호는 처음으로 관측되었으며, 이때 관측된 초음파신호는 정극성 최대치에서 검출할 수 있었다. 전압이 상승함에 따라 정극성이 부극성에 비해 초음파의 발생빈도는 높게 나타났으며, 초음파신호의 크기는 전류펄스의 크기에 비례하였다. 그리고 초음파 펄스수는 방전전하량에 비례하여 증가된 것으로 나타났다. 옥외 전력기기에 대한 초음파 측정시 기본데이터를 얻기 위해 초음파의 발진 및 수신장치를 이용하여 공중초음파의 감쇄, 시간지연 및 지향특성도 조사하였다.