Consequence Analysis of the Fire & Explosion on the Flammable Liquid Handling Facility and LPG Station

제 4류 위험물 취급소 및 LPG 충전소의 화재$\cdot$폭발 피해 영향분석

  • Lee Su-Kyung (Dept. of Safety Engineering, Seoul National University of Technology) ;
  • Lee Chang-Wook (Dept. of Safety Engineering, Seoul National University of Technology)
  • 이수경 (서울산업대학교 안전공학과) ;
  • 이창욱 (서울산업대학교 안전공학과)
  • Published : 1999.06.01

Abstract

The XX company that is handling the class IV hazardous materials, located in Bu-Chon City and the LPG station in front of the XX company which is about 20 meters apart, was chosen as the standard model for this study In carrying out the consequence analysis, PHAST and Super-Chems were used for the study and utilizing the output of the simulation, we have evaluated the consequences throughout the probit analysis and explosion overpressure analysis. In case of Acetone, the effect distance of the damage on facilities-that is the result of radiation heat flux of $37.5kW/m^2$ by TNO model-is 68.51m by PHAST model and 40.93m by Super-Chem model. The risk assessment of the LPG station which is based on the explosion resulted as the analysis of the fire ball showed the diameter 125.2m, the height 206.2m and the duration 11.28sec and the effect distance for the radiant heat flux $37.5kW/m^2$ was 137.0m.

본 연구에서는 경기도 부천시 OOO소재의 위험물 판매 취급소인 XX상사를 표준모델로 선정하여 여기서 취급하는 제 4류 위험물에 대한 위험성 평가를 실시하고 아울러 바로 길건너 맞은편의 약 20m 거리에 위치한 LPG 충전소에 대한 위험성 평가도 아울러 실시하였다. 본 연구에서의 위험성평가를 위해서는 PHAST와 Super-Chem 소프트웨어를 이용하였으며 이러한 Simulation 결과를 이용하여 분석한 결과 물질 중 아세톤의 경우 TNO 모델에 의한 복사열 평가에 의해 설비에 손상을 줄 수 있는 $37.5kw/m^2$에 해당하는 거리는 PHAST 모델의 경우 68.51m에 이르렀으며, Super-Chem 모델의 경우는 40.9,3m에 이르렀다. LPG 충전소에 대한 Simulation 결과 Fireball 지름은 125.2m에 이르며 Fireball의 높이는 206.2m에 이른다. 또한, 그 지속시간은 11.28초로 계산되었다.

Keywords