Acknowledgement
Supported by : 김해발전연구소
(Department of Occupational Safety and Health, College of Health Sciences, Inje University)
(인제대학교 보건대학 산업안전보건학과)
In order to evaluate and improve the performance of local exhaust ventilation systems for two TCE degreasing (A, B) and two electroplating (C, E) and one acid dipping & plating (D) operations located in Kimhae, the performance test was conducted with trace gases and a thermal anemometer (Kanomax 24-6111, Japan). For the inadequately designed systems, the improvement and redesigns in compliance with recommendation by ACGIH was suggested. The results of performance test for each system are as follows; 1. System of Workplace A was generally well-designed. Actual exhaust air flow rate was in excess of 68% above the recommended standard exhaust air flow rate. 2. System of Workplace B was very well-designed and completely enclosed. 3. All systems of Workplace C including hoods were poorly-designed and actual exhaust air flow rates were insufficient for open tanks. All systems should be upgraded according to ACGIH recommendations. 4. Supply and exhaust air flow rate of push-pull exhaust systems in Workplace D should be greatly increased. The width of flange of dipping tank hood should be increased with the value suggested. 5. System of Workplace E was well-designed. Actual exhaust air flow rate was in excess of 54% above the required.
Supported by : 김해발전연구소