In this paper, the electric property was investigated for insulation diagnosis of radiation of EPR electric power cables by partially irradiation with $^{60}Co-{\gamma}$ rays. As the rate of radiation increased from 100Mrad to 200Mrad, charging current and discharging current were increased from $1.03{\times}10^{-7}$(A) to $4.3{\times}10^{-9}$(A). In addition, we found charging current and discharging current of cables subjected to 50% and 16.7% irradiation changed the length of the part 1/2 to 1/6 as in comparison with cables degraded by 100% irradiation. For 22m and 66m of cables which had not been degraded yet, we realized the value of charging current and discharging current of 66m cables is three times higher than 22m cables. From these results, it is demonstrated that the possibility of utilizing charging current and discharging current as the diagnosis method of insulation degradation with irradiating EPR cables by $^{60}Co-{\gamma}$ rays.

이 논문은 원자력발전소에서 사용되고 있는 부분적으로 방사선 조사된 EPR 전력 케이블의 방사선 절연열화 진단을 행하기 위해서 전기특성을 조사한 것이다. 본 연구에서는 방사선 조사량을 100Mrad부터 200Mrad까지 증가시킨 케이블 시료를 열화비율에 따른 방사선 조사량에 의한 충전전류 및 방전전류를 측정한 결과 $4.3{\times}10^{-9}$(A)로부터 $1.03{\times}10^{-7}$(A)로 증가함을 알 수 있었다. 또한 100% 일때의 충전전류 및 방전전류를 50%, 16.7% 일때를 비교하면 후자의 케이블은 열화된 부분의 길이가 1/2, 1/6로 되므로 충전전류 및 방전전류로 1/2, 1/6로 흐름을 알 수 있었다. 열화하지 않은 22m와 66m의 케이블을 조사한 결과 66m의 케이블 시료쪽이 충전전류 및 방전전류 값이 22m 케이블보다 3배나 크다는 것을 확인했다. 이들 결과로부터 방사선을 조사한 EPR 케이블의 절연열화 진단법으로 충전전류 및 방전전류를 측정하는 것이 가능하다는 것을 확인했다.