Evaluation of Popping Performance of Safety Valves in City Gas Facilities

도시가스시설에서 안전밸브의 분출성능에 관한 평가 연구

  • 김영규 (한국가스안전공사 가스안전기술연구센터) ;
  • 김청균 (홍익대학교 기계공학과)
  • Published : 1998.06.01

Abstract

In order to evaluate the performances of safety valves for low pressure, the popping pressure and flow rate of the natural gas have been investigated. The measured results of the popping pressure show that there is a big scattering depending on the manufacture year of a safety valve. And sample A showed the ideal popping pressure mode compared to other B and C samples. The popping flow rate of the safety valve is proportional to the seat size as the inlet pressure increases. These results may be used as a guideline for a design and diagnosis of the safety valve.

Keywords