Enhancement of thin film evaporation on low-fin tubes

낮은핀관의 액막 증발 촉진에 관한 연구

  • Published : 1998.11.01

Abstract

In this study, thin film evaporation of water on low-fin tubes were experimentally investigated. Five low-fin tubes with different fin spacing and fin height were tested. Test range covered 0.146kg/ms $\leq$$\Gamma$$\leq$0.219kg/ms and 10㎾/$\m^2$$\leq$q $\leq$70㎾/$\m^2$. Saturation temperature was loot. Compared with the plain tube, low fin tubes enhanced the water film evaporation from 60% to 100%. Tubes with fin spacing smaller than 2mm and fin height higher than 1mm performed better than tubes with other fin configuration. However, when fin spacing was too small at high film flow or fin height was too high at low film flow, the performance decreased. The heat transfer coefficient slightly increased as the flow rate increased. Correlations are developed based on present data.