Abstract
This paper deals with the power frequency electric and magnetic profiles from transformer and gas-insulated swichgear(GIS) perimeters in the indoor power substation. Measurements of electric and magnetic field magnitudes were carried out by using single axis and three axes field meters at a height of 1[m]. The resultant electric and magnetic field profiles measured in the vicinity of the transformer were displayed as a 2-dimensional plot. The electric fields intensity are relatively low value of about 2.3~9[V/m], and the magnetic fields intensity range from 0.3 to [$20.3\mu$T]. Also, in the GIS perimeter the electric fields intensity are in the range of 2.2~2.5[V/m], and the high magnetic fields are largely localized to the intermediate section of the GIS and their amplitudes are [$1.2~39.5\mu$T]. Metal enclosures of transform and GIS play a role in reducing the electric field, and the magnetic fields are characterized by a rapid decrease with distance from the transformer and GIS enclosures.
이 논문은 옥내 변전소의 변압기와 가스절연개폐장치(GIS) 주변에서 상용주파수의 전장과 자장의 분포에 관한 것으로 전장과 자장의 측정은 지표상 Hill]의 높이에서 1차원과 3차원 측정기로 수행되었다. 변압기 주변에서 전 장과 자장의 분포는 2차원적 평면도로써 나타내었으며, 전장의 세기는 2.3~9[v/m]으로 비교적 작은 값이었고, 자장의 세기는 $0.3~20.3[{\mu}T]$이었다. 또한 GIS의 주변에서 전장의 세기는 2.2~2.5[V/m]이고, 자장의 세기는 주 로 GIS의 중간부위에서 국부적으로 크게 나타났으며 $1.2~39.5[{\mu}T]$의 값이었다. 변압기와 GIS의 금속 외함은 전장을 감소시키는 역할을 하고, 자장은 변압기와 GIS의 외함으로부터 거리에 따라 급속하게 감소하는 특정을 보이고 있다.