Effect of the Cross Magnetizatin Saturated Generators on the Analysis of Steady State Stability

정태안정도 해석에 미치는 발전기 교차자화 포화특성의 영향

  • Published : 1998.05.01

Abstract

This paper presents a modeling of a synchronous machine infinite bus system of which not only seperated saturation effect but also cross magnetization effect of the saturated generator is included for the more precise analysis of the system. In the process of reforming the flux linkage equations of the state equations which have generator saturation effects, the d-axis coordinated system of a generator is fixed that the d-axis proceeds the q-axis in $90^{\circ}$ to accord with the generally accepted generator model used before. The simulation results show that cross magnetization has a very important effect to the more precise eigenvalue analysis of steady state stability.bility.

본 논문에서는 발전기의 특성을 보다 정확히 해석하기 위해 발전기의 상세모델에 동일축 전류성분에 의한 포화특성과 교차자화에 의한 포화특성을 고려한 상태방정식을 발전기의 전류모델에 대하여 제시하였다. 발전기의 포화특성을 종래의 동일축성분 전류에 의한 포화특성 뿐만 아니라 교차자화 효과에 의한 포화특성까지도 고려할 수 있도록 각 경우의 자속쇄교수와 전류의 관계를 나타내는 인덕턴스 행렬의 표현식을 보였으며, 발전기를 해석하기 위한 기준 좌표계로 발전기의 d축이 q축보다 위상이 $90^{\circ}$앞서는 좌표계를 사용하여 관계식을 재정립함으로써 정태안정도 해석에 사용하던 기존의 발전기모델과 일치하도록 한였다. 사례연구를 통해서 보다 정확한 안정도 해석을 위해서는 교차자화 효과를 고려한 발전기 모델이 계통해석에 사용되어야 함을 입증하였다.

Keywords

References

  1. Power System Control and Stability P.M. Anderson;A.A. Fouad
  2. IEEE Transactions on Energy Conversion v.3 no.4 Experimental Study of the Saturation and The Cross-Magnetizing Phenomenon in Saturated Synchronous Machines A.M. El-Serafi;A.S. Abdallah;M.K. El-Sherbiny;E.H. Badawy
  3. IEEE Transactions in Energy Conversion v.6 no.3 Effect of Saturation on The Steady-State Stability of A Synchronous Machines Connected to An Intinite Bus System A.M. El-Serafi;A.S. Abdallah
  4. Power System Stability and Control P. Kundur