Measurements of Electric and Magnetic Fields in the Vicinity of Transmission Lines and Electric Appliances

송전선로 부근과 가전제품의 전자계 측정

  • 김상범 (한국전력공사 전력연구원) ;
  • 조성배 (한국전력공사 전력연구원) ;
  • 이동일 (한국전력공사 전력연구원) ;
  • 신구용 (한국전력공사 전력연구원) ;
  • 김정부 (한국전력공사 전력연구원)
  • Published : 1998.10.01

Abstract

In spite of increasing public concern about the human exposure to electric and magnetic fields(EMFs), there is little information about the EMF levels in the vicinity of power facilities and of home appliances. To provide such information, a nationwide survey for EMFs near overhead transmission lines has been conducted. The median values of the electric fields and magnetic fields of 153 transmission lines were 0.47 kV/m and 11.6 mG, respectively. The maximum values were 3.16 kV/m and 125 mG. These were low values in comparison with any EMF guidelines or standards of advanced contries. Measurements of the magnetic fields of typical home appliances and daily human exposure records have been also conducted. These magnetic field values were comparable to those of the transmission lines.

최근 국내 전력설비에서 발생하는 전자계에 대한 관심이 증가하고 있지만 이에 대한 정확한 자료 파악은 극히 미미한 실정이다. 본고에서는 송전선로에서 발생하는 전계와 자계의 수준을 알아보기 위하여 전국 1537H의 송전 선로를 대상으로 전계와 자계를 측정하였다. 측정 지점의 전계와 자계 최대치들의 중간값은 각각 0.47 kV /m, 11.6 mG 최고 값은 각각 3.16 kV /m, 125 mG로 나타났으며, 전세계의 전자계 관련 권고치나 기준치에 비해 낮은 값임을 알 수 있었다. 아울러 몇 가지 경우에 대하여 가전제품에서 발생하는 자계와 일일 자계 노출량올 측정 하였고 이를 송전선로의 자계 크기와 비교하였다.

Keywords

References

  1. Presented at The International Conference on High-Tension Electric Systems Influence of the electric field in 500 and 750kV swichyards on maintenance staff and means for its protection Korobsova V;Morozov Y;Stolorv M;Yacub Y
  2. British Journal of Industrial Medicine v.42 Health of workers exposed to electric fields Broadbent DE;Broadbent MHP;Male J;Jones MRL
  3. Am. J. Epidemiol v.111 no.4 Electrical wiring configurations and childhood cancer N. Wertheimer;E. Leeper
  4. Scandinavian Journal of Work and Environmental Health v.15 Association of childhood cancer with residential traffic density D. A. Savitz;J. Chen
  5. Am. J. Epidemiol. v.134 Exposure to residential electric and magnetic fields and risk of childhood leukemia S. London;K. Thomas;J. Bowman;E. Sobel;J. Peters
  6. Am. J. Epidemiol. v.138 Magnetic fields and cancer in people residing near Swedish high-voltage power lines M. Feychting;A. Ahlbom
  7. EPRI Journal EMF in American homes Electric Power Research Institute
  8. EPRI Journal Managing magnetic fields Electric Power Research Institute
  9. Bioelectromagnetics v.16 Magnetic field exposure among utility workers T. D. Bracken;R. F. Rankin;R. S. Senlor;J. R. Alldredge;S. S. Sussman
  10. 과천 송전선로 전자계 보고서 과천시 한국전력공사
  11. 한국환경위생학회지 v.23 no.1 극저주파 영역에서의 전자파 노출에 관한 조사 연구 김윤신(외3인)
  12. 기술보고서, TM.96EJ29.I.1997.1194 송전선로 전자계 계산 프로그램 한국전력공사 전력연구원
  13. 기술보고서, TM.96EJ29.I.97.211 송전선로 전자계 영향 연구(Ⅰ) 한국전력공사 전력연구원
  14. ICNIRP Guidelines Guiedelines for limiting exposure to time-varying electric, magnetic, and electromagnetic fields up to 300 GHz International Radiation Protection Association;International Commission on Non-Ionizing Radiation Protection
  15. ICNIRP Guidelines Guidelines for limiting exposure to time-varying electric, magnetic, and electromagnetic fields up to 300 GHz International Radiation Protection Association;International Commission on Non-Ionizing Radiation Protection
  16. European Prestandard, ENV 50166-1 Human exposure to electromagnetic fields:Low-frequency(0Hz to 10 kHz) European Committee for Electrotechnical Standardization