Degradation Diagnosis by Void Defects Using a Neural Network

신경망을 이용한 보이드 결함에 의한 열화진단

  • 최재관 (광운대학교 신기술연구소) ;
  • 김성홍 (광운대학교 신기술연구소) ;
  • 김재환 (광운대학교 신기술연구소)
  • Published : 1998.10.01

Abstract

In this paper, we obtained the data, which is required in training the neural network and diagnosing the degradation degree, by introducing the AE detection that is effective method in ordinary degradation diagnosis on activation. Aa the results of generalization tests by appling neural network to the unknown AE patterns obtained from two kinds of specimen, firstly as to evaluate an objective performance of neural network, the recognition ration for no-void specimen and 1[mm] -void specimen are appeared to be 98.9% and 92.5%, respectively. Also, in the evaluation of the adaptability of neural network with a new type of 0.2[mm] -void specimen, it is confirmed that the result appears to be 64% of recognition ratio at 94% of confidence interval coefficient in expectation output 0.2. On the other hand, the recognition capability of the neural network was confirmed by data from no-void and 1[mm] void specimen. The results prove the promising possibility of the application of ANN to discriminate specific void affecting as main degradation source at partial discharge condition in insulator containing multi-void by accummulated data base.

Keywords

References

  1. Electrical Degradation and Breakdown in Polymers L. A. Dissado;J. C. Fothergill
  2. Conf. Rec. 1992 IEEE Inter. Symp. Elect. Insul. Diagnostics of Insulation Systems using Statistical Tools E. Gulski;F. H. Kreuger
  3. IEEE Trans. Elect. Insul. v.28 no.6 Neural Networks as a Tool for Recognition of Partial Discharge E. Gulski;A. Krivda
  4. IEEE Trans. Elect. Insul. v.27 no.3 Discrimination of Partial Discharge Patterns Using a Neural Network N. Hozumi;T. Okamoto;T. Imajo
  5. IEEE Trans. Elect. Insul. v.27 no.1 Computer-aided recognition of Discharge Sources E. Gulski;F. H. Kreuger
  6. Trans. Insul. Elect. Eng. Japan v.102 no.12 Change in Pulse-Mean Φ-Q Distribution Patterns of Partial Discharge due to Treeing Propagation T. Okamato;T. Tanaka
  7. KIEE v.10 no.3 부분방전 전하와 음향방출 펄스의 동시 측정에 의한 트리잉 파괴진단 김성홍;박재준;김재환