Air-side flow and heat transfer for a two-row lanced finned tube heat exchanger

2열 절개형 핀-관 열교환기의 공기측 유동 및 열전달 특성

  • Published : 1998.01.01

Abstract

A numerical study has been performed to obtain the air-side flow and heat transfer characteristics for a two-row lanced finned tube heat exchanger with 7 mm tube outer diameter. The increases of dimensionless local heat flux at the leading edge of slit and bottom surface of the fin were noticed. The temperature of air at downstream of the 2nd row of the lanced fin becomes more uniform than that of the plain fin because the mixing of energy increases by the slit and the side-slit. As the inlet velocity increases, the contribution of the 1st row to heat transfer decreases and that of 2nd row increases.

Keywords