Evaluation on the Aggressivity of Drinking Water for Corrosion Control in Water Distribution System

상수도관로의 부식 방지를 위한 수돗물의 침식성 평가

  • Published : 1997.01.15

Abstract

The corrosion problems in water distribution system are reduced by decreasing the agressivity of drinking water which is evaluated by marble test and saturation indices(LSI or CCPP etc.). Marble test is a reliable method to determine the actual saturation condition of treated water. This study was done to determined the aggressivity of tap water and the effectiveness of $Ca(OH)_2$ and NaOH dosage for corrosion control. The drinking water in Seoul were evaluated by marble test and Langelier Index(LSI) and Calcium Carbonate Precipitation Potential(CCPP). The results indicated that the drinking water in Seoul were undersaturated as Calcium Carbonate($CaCO_3$). The LSI and CCPP of the water treated with $Ca(OH)_2$ were higher than that of water treated with NaOH. Therefore, to increase the Alkalinity and Calcium Hardness for corrosion control in water distribution system, $Ca(OH)_2$ is more effective than NaOH.

Keywords