An experimental investigation of thermodynamic performance of R-22 alternative blends

R-22 대체용 혼합냉매의 열역학적 성능에 대한 실험연구

  • 황의필 (아주대학교 대학원 기계공학과) ;
  • 김창년 (아주대학교 대학원 기계공학과) ;
  • 박영무 (아주대학교 기계 및 산업공학부)
  • Published : 1997.02.01

Abstract

R-410a and R-407c witch have the best potential among the substances being considered as R-22 alternatives were tested as "drop in" refrigerants against a set R-22 baseline tests for comparison. The performance evaluations were carried out in a psychrometric calorimeter test facility using the residential split-type air conditioner under the ARI rating conditions. Other than the use of different lubricant and a hand-operated expansion valve, one of the commercial systems was selected for the experiment. Performance characteristics were measured; compressor power, capacity, VCR, mass flow rate and COP. The tests showed that R-407c can be directly applied to the existing refrigeration system because of its similar vapor pressure and other thermopysical properties with those of R-22. However, it required change to the volume flow rate of compressor in order to achieve the similar performance with R-22 because of its relatively small VCR and capacity. Meanwhile, R-410a has too high a vapor pressure to be applied to the existing system and this feature results in relatively low COP of the system compared to that of R-22. But this could be improved by changing compressor design considering R-410a's relatively high VCR and capacity compared to those of R-22.

Keywords

Acknowledgement

Supported by : 과학재단