초록
Recently scientists and engineers are developing a system to get waste heat of low-temperature level with advanced heat pump, which have not been used up to now. As the reason, it is necessary to examine capability of using waste heat which is raised up in the tunnel of subway out of widely distributed low-temperature waste heat in large cities. Therefore we surveyed thermal environment of the tunnel of subway in $S\check{o}my\check{o}n$, downtown of Pusan, from November 1995 to December 1996 and developed a program to predict the thermal environment of subway on the basis of experimental data and the geometries of tunnels. This paper has proved availability of waste heat of subway when the measured results obtained in subway in the winter time and the simulated results of thermal environment prediction program are compared, as well as has reported results of estimating reliability of the simulation program. As the result, the charateristics of thermal environment in the tunnel of subway in $S\check{o}my\check{o}n$ station in the winter time are to be followed; 1) temperature in the tunnel is about $10^{\circ}C$ higher than outside air temperature, 2) temperature change in the tunnel is less than that in the platform so that we may obtain stable heat source, 3) and when the measured results obtained in subway in the winter time and the simulated results of thermal environment prodiction program is compared, both results show similar tendency. Therefore, we confirm estimating reliability of the simulation program.