A Study on the Thermal Response Characteristics of Snow Removing Facilities using Heat Pipe

히트파이프식 제설설비의 열응답 특성에 관한 연구

  • Published : 1997.12.30

Abstract

The purpose of this research was to study the characteristics of heat transfer of snow removing facilities using heat pipe by experimental method. Heat pipes was constructed a flexible tube connected between evaporator and condenser ends for altitude adjustment of evaporator and it was constituted an internal diameter of 25.4mm, a length of 950mm for heating section and a length of 6000mm for condenser section with copper material for closed system. The results showed that the effect of heat transfer was increased when inclination angle and inlet temperature of heating water increased. Wall temperature response by inclined angle $4.5^{\circ}c-9^{\circ}c$ and working fluid amount 0.96 from to 1.3 times of evaporator volume were better than those of other working fluid and angle.

본 연구는 제설설비에 히트파이프를 사용할때 기술적, 경제적 문제에 대해서 고찰하고, 히트파이프식의 제설구조물를 제작 설비하는 경우의 적용범위와 작동조건에 따라 전열효과를 실험적으로 검토한 것이다. 제설 제빙용으로 개발된 히트파이프식 설비는 히트파이프 배열의 피치에 관계없이 상호보완적으로 작동하였으며 제설설비를 위해 충분한 성능을 보였다. 작동액체의 충전량은 증발기의 체적을 기준으로 하여 $0.96{\sim}1.3$배인 경우가 가장 적합 하였다. 가열액체의 온도가 증가할수록 안정한 운전이 가능하였고 경사도는 4.5도에서 9도사이가 가장 양호했다. 경사가 크고 가열매체 입구온도가 증가할 때 온도진동수는 증가하고 진폭은 감소하고 열전달 효과는 크게 나타났다.