Assessment of Post-LOCA Radiation Fields in Service Building Areas for Wolsong 2, 3, and 4 Nuclear Power Plants

월성 원자력 발전소 2,3,4호기에서의 LOCA 사고후 보조건물의 방사선장 평가

  • Published : 1995.03.30

Abstract

The radiation fields following the large loss of coolant accident (LOCA) have been assessed for the vital areas in the service building of Wolsong 2, 3, and 4 nuclear power plants. The ORIGEN2 code was used in calculating the fission product inventories in the fuel. The source terms were based upon the activity released following the dual failure accident scenario, i.e., a LOCA followed by impaired emergency core cooling (ECC). Configurations of the reactor building, the service building, and the ECC system were constructed for the QAD-CG calculations. The dose rates and the time-integrated doses were calculated for the time period of upto 90 days after the accident. The results showed that the radiation fields in the vital access areas were found to be sufficiently low. Some areas however showed relatively high radiation fields that may require limited access.

월성 원자력발전소 2,3,4 호기의 보조건물 주요 지역에서 냉각재 다량상h7사고 (large LOCA) 후의 방사선장을 평가하였다. 핵분열 생성물의 총량은 ORIGEN2 코드를 사용하여 계산하였고 선원항은 2중고장 시나리오, 즉 LOCA 사고후 비상노심냉각 (ECC) 계통의 고장이 결부된 사고시의 방사능 방출에 근거하였다. 원자로건물, 보조건물 및 ECC 계통의 구조모형을 QAD-CG 모델에 포함하여 계산하였다. 사고시점부터 90일 경과시까지 시간대 별로 선량율과 누적선량을 계산하였다. 결과적으로, 연속출입이 요구되는 중요지역에서의 방사선장은 충분히 낮은 것으로 평가되었다. 그러나, 일부구역에서는 제한적인 출입을 허용할 정도로 상대적으로 높은 방사선장을 나타내었다.

Keywords