Fire Growth of Wood Cribs and Available Safe Egress Time

목재연소시의 실내화재성상과 안전대피시간

  • 정길순 (충북대학교 대학원) ;
  • 태순호 (서울산업대학교 산업안전공학과) ;
  • 이병곤 (충북대학교 산업안전공학과)
  • Published : 1993.06.01

Abstract

Available Safe Egress Time(ASET) is the time available for occupants to evacuate safely In compartment fire, and It depends on the time of fire detection and hazardous conditions. The purpose of thls study Is to provide an analytical basis and experimental data for estimating the fire growth in compartments and the available safe egress time, and to compare the experimental data with those proposed equations. As a result, hazard order Is poison to CO, descent of smoke layer, poison to $CO_2$, burn to hot smoke layer, and lack of $O_2$, ASET is lengthened in this order. Also, The more fire load is increased, the more ASET is shorted.

Keywords