An Experimental Study on the Cut off Performance Test of Cut off Type Overflow Valve in L.P Gas

과류(過流) 차단형(遮斷型) 액화(液化) 석유(石油)가스 용기용(容器用) 밸브의 차단(遮斷) 성능(性能) 시험(試驗)에 관(關)한 실험적(實驗的) 연구(硏究)

  • 이진 (대림전문대학 기계과)
  • Published : 1992.05.01

Abstract

The purpose of this paper is to determine the cut off flowrate regions of the overflow valve in using L.P gas vassels. The experimental methods were employed to measure the cut off flowrate in the state of constant pressure by using the $N_2$ gas. 1) To determine the optimum cut off flowrate regions, Hose length are required 0.5 meters. 2) Cut off fowrate regions about the each pressure can be suggested as follows. A) Cut off flowrate rigions are $2.0-4.0m^3/hr$ at the pressure of the $1Kg_f/cm^2$. B) Cut off flowrate rigions are$7.0-10.0m^3/hr$ at the pressure of the $10Kg_f/cm^2$.

Keywords