Acknowledgement
Supported by : 한국과학재단
A theoretical cycle analysis has been performed for a basic heat pump, charged with non-azeotropic refrigerant mixtures, R22/R114 and R13B1/R152a. At first, a procedure is introduced to calculate thermodynamic properties simply and correctly, and the advantages of using refrigerant mixtures are discussed through the cycle analysis. It is shown that by using refrigerant mixtures in the heat pump, several improvements can be made. In comparison with conventional pure refrigerants, the application of refrigerant mixtures results in high reliabilities caused by the extension of the application limit, energetic improvements, and a continuous capacity control. From generalizing various results, the optimum compositions in refrigerant mixtures are also determined. The 30%/70% and 40%/60% compositions are selected for R22/R114 and R13B1/R152a, respectively.
Supported by : 한국과학재단