Abstract

A study has been conducted experimentally on heat transfer characteristics of louvered fin heat exchangers with various fin spacings in air. The experimental results are as follows; 1. Mean heat transfer coefficient is increased with increasing air velocity and the optimum fin spacing shows at S=5mm. 2. Pressure drop is increased with increasing air velocity and its maximum value shows at S=3.5mm and its minimum value shows at S=6mm. 3. $\bar{h}/{\Delta}P$ is decreased with increasing air velocity and its maximum value shows at S=5mm and its minimum value shows at S=3.5mm.