A Study on the Performance of an Absorption Heat Transformer with Process Simulation

프로세스 시뮬레이션에 의한 제 2종 흡수식 열펌프 성능에 관한 연구

  • 조승연 (한국과학기술원 기계공학부) ;
  • 김영인 (한국과학기술원 기계공학부)
  • Published : 1987.06.01

Abstract

The purpose of this study is to develop a computer model for simulating the water-lit hium bromide absorption heat transformer (AHT) Including all major components and to find the flexibility in operation. The effect of source hot water temperature, cooling water temperature, useful hot water flow rate, cooling water flow rate and evaporator circulation flow rate were investigated. The coefficient of performance (COP), temperature boost $({\Delta}T\;=\;T_A\;-\;Ti)$ and concentration variations can be predicted. The performance study indicates that the performance of AHT increases for the waste hot water temperature increasing and with a decrease of the cooling water temperature. The effect on performances of useful hot water flow rape is significant except on temperature boost. Also the effects on performance of cooling water flow rate and evaporator circulation flow rate are small. It is shown that the computer program is valuable to predict the performance of absorp-tion heat transformer units at various working corditions.

Keywords