Experimental Study on the Coefficient of Performance of a Small Absorption Refrigerator

소형 흡수식 냉동기의 성적계수에 관한 실험적 연구

  • 이선규 (한국과학기술원 기계공학과, 광림기계주식회사) ;
  • 김상수 (한국과학기술원)
  • Published : 1987.04.01

Abstract

The purpose of this research is to study the characteristics of the coefficient of perform-ance (COP) of the small absorption refrigeration system. This experimental study is performed with two selected variables, the temperature of the generator and the input temperature of the cooling water. In order to determine the input temperature of the generator which gives maximum COP, the experimental data are obtained with controlling the temperature of the generator in the range of $20-32^{\circ}C$ of the temperature of the cooling water. The range of the generator heat suppling temperature which gives maximum efficiency is about $90-95^{\circ}C.$ The temperature range depends on the characteristics of the equipment unit. The most important result in this experiment is the trends of the COP in accordance with the variation of these temperatures. This trend will furnish the informations and knowledges for designing and operating the absorption refrigerator.

Keywords