강내치료실 차폐에 대한 고찰

A Study on Structural Shielding Design of Afterloading Therapy Room

  • 윤석록 (경희대학교 의과대학 부속병원 치료방사선과) ;
  • 김명호 (경희대학교 의과대학 부속병원 치료방사선과) ;
  • 신동오 (경희대학교 의과대학 부속병원 치료방사선과)
  • Yun, Suk-Rok (Dept. of Therapeutic Radiology, Kyung Hee University Hosp.) ;
  • Kim, Myung-Ho (Dept. of Therapeutic Radiology, Kyung Hee University Hosp.) ;
  • Shin, Dong-Oh (Dept. of Therapeutic Radiology, Kyung Hee University Hosp.)
  • 발행 : 1987.06.01

초록

In the case of designing a high dose rate remote controlled afterloading treatment room with existing hospital facilities. We must construct the effective protective barriers so as to reduce the primary and scattered radiation up to the maximum permissible dose level. It is difficult to reinforce the barrier thickness of the shielding requirements because of the limited space and the problem of the existing building structure at the surrounding area. Therefore we can reduce the intensity of primary radiation to the required degree at the location of interest with installing the appropriate I shaped Pb barriers between the radiation source and the shielding wall of the concrete. As a result, it was possible to reduce the intensity of the primary radiation below the M.P.D level by using additional Pb barriers instead of increasing thickness of concrete wall.

키워드