A Study on The Drying and Hot Water System Using Condensation Waste Heat

응축폐열을 이용한 건조 및 온수장치에 관한 연구

  • 박노현 (농어촌개발공사 종합식품연구원) ;
  • 고하영 (농어촌개발공사 종합식품연구원) ;
  • 정진웅 (농어촌개발공사 종합식품연구원) ;
  • 강통삼 (농어촌개발공사 종합식품연구원)
  • Published : 1986.12.01

Abstract

In the normal Refrigeration process, the condensation heat of refrigerant s not been used because of its low-temperature waste heat. To recover the condensation waste heat of R-12 refrigerator, a drying and hot water system was designed and experimented. The results obtained were summarized as follows: 1. As the temperature a temosphere was increased, the temperature of discharge gas of compressor was increased. And the temperature was $80-84^{\circ}C$ for air condensing type and was $68-71^{\circ}C$ for water condensing type during summer. 2. The condensation waste heat could be obtained up to $50-55^{\circ}C$ of drying heat-source and Hot water in summer. In this case, recovered rate was about $73\%$. And the more temperature of drying Heat-source and Hot water were increased, the more a recovered rate were decreased. 3. When comparing drying characteristics of Agro-products in dryer of waste heat utilization and Hot air, there was no quality difference in products. But drying time of the former was 3 Hours longer than the latter. 4. The condensation waste heat of compressor could be applied into the drying of marine products, the predrying of agro-products and making hot water. And showed high possibility of the waste heat using in low-temperature storage.

Keywords