우리나라에서의 증발식 냉각의 효용성

  • Min, Man-Gi
  • 민만기 (고려대학교 이공대학 기계공학과)
  • Published : 1974.09.01

Abstract

The effectiveness with which evaporative cooling can be used in Korea was analysed by making use of weather data of 15cities in a past decade. In ASHRAE comfort chart for a still air atmospheric condition was divided into two dimensional array, 14 zones by effective temperature and 10 zones by relative humidity, and all hours of weather condition in those zones were. computed from every 4 hours weather data in a past decade. From this computation obtained were for 15 cities : 1. average annual total hours above $23^{\circ}C$ ET 2. effective temperatures with $5\%$ excess factor, and 3. ratios of all hours in wet (above $25.6^{\circ}C$ WBT), intermediate $(22^{\circ}C\;to\;25.6^{\circ}C\;WBT)$, and dry $(below\;22^{\circ}C\;WBT)$ area to total hours in whole area on comfort chart beyond $23^{\circ}C$ ET to effective temperature of $5\%$ excess factor. It was shown from this computational result that in Korea evaporative cooling was not effective for building and residential comfort air conditioning but could be useful for comfort air conditioning in industry and industrial air conditioning, depending upon the air stream velocity and the type of application.

Keywords