In December 2017, a fire at the Jecheon Sports Center caused 29 deaths and 40 injuries, and about 2 billion won in property damage. It is a facility used by unspecified people as a publicly used establishment with a piloti structure. The damage was expanded due to the ignition of combustible exterior materials, Lack of fire protection in horizontal and vertical penetrations. Although legislation has improved since the fire, it is not retroactively applied, increasing the risk of fire in existing buildings. Accordingly, it is necessary to examine the case of the Jecheon Sports Center fire and draw out the problems. In this study, the fire simulation results and the Jecheon Sports Center fire are comparatively analyzed and used as basic data for fire reduction measures in publicly used establishment. As a result of the fire simulation drive, in the case of the second floor, the room temperature exceeded the human life safety standard of 60 ℃ after about 700 seconds had passed. In the case of three floor, it is predicted that the indoor temperature will exceed about 350 ℃. and temporary complexation will occur in the indoor combustibles.