A Health Index of Aged Undeground MV Cables in Domestic

경년열화된 지중 MV급 케이블의 Aging Index

  • Published : 2015.07.15

Abstract

In this study, the author apply the VLF(Very Low Frequency) tan-delta data that has been measured at each office of the KEPCO 2012 to the Weibull distribution which is the statistical analysis as previous studies for the remaining life prediction through the improvement of the sensitivity and reliability of the degradation state assessment of underground distribution power cables. Also, in this paper, UCD(Used Cable Diagnosis) Matrix proposed by KEPCO was applied to the hierarchy of assessment prioritization. it suggests Aging Index for condition assessment and high reliability of proper economic replacement cycle using the weight according to the assessment prioritization.

Keywords