A study on the Relationship between Load Current and Temperature of 6.6 kV Cable Systems in Operation
운전중 6.6kV 케이블 시스템의 부하전류와 온도의 상관관계 연구
- Lee, Kwan-Woo (Osung Mega Power) ;
- Hwang, Yung-Ha (Korea Western Power Co., Ltd) ;
- Lee, Sang-Hun (Korea Western Power Co., Ltd) ;
- Um, Keehong (Hansei University)
- Published : 2015.07.15
Abstract
This work is to study the effect of load current on 6.6 kV power cables in operation. In order to figure out the relationship between load current and temperature of the power cables, we have developed measuring equipment for insulation resistance, temperature, and current tested on 9 cables at power station, Western Power Co. Ltd. The cables used in our test were in operation for the last 18 years. Our research over a year showed that the remaining lifetime of 8 cables was more than 20 years. The remaining lifetime of one cable was about 16 to 18 years.